Menu
Your Cart

Mersen 83120138 STPT12-12K275V-4PG Three Phase Type 1+2 Surge Arrester

Mersen 83120138 STPT12-12K275V-4PG Three Phase Type 1+2 Surge Arrester
EV Ready
Mersen 83120138 STPT12-12K275V-4PG Three Phase Type 1+2 Surge Arrester
  • Approvals and Standards

    IEC 61643-11
    EN 61643-11

    Key Features and Benefits

    STP T12 12.5 is the series of combined Type 1+2/Class I+II devices for discharging lightning currents and protecting against voltage surges, in accordance with EN/IEC 61643-11. Suitable as the first step of protection in incoming power supply panels and areas with exposure to the atmosphere, where installations are usually provided with an external lightning protection system.

    Lightning impulse current (10/350μs): 12.5kA per phase
    Maximum discharge current (8/20μs): 50kA per phase
    Nominal discharge current (8/20μs): 20kA per phase
    TNS, TNC, TT and IT networks
    Un(L-N/L-L): 60V, 120/208V, 230/400V, 277/480V and 400/690V
    DIN-rail mountable, plug-in format
    Visual and remote end of life indicators
    Reversible chassis to allow cable entry from above or below
    Mechanically coded cartridges to avoid cartridge replacement errors
    Back-up fuse: 200 A gG

    Applications

    Industry and automation
    Commercial and residential installations
    Telecom & IT & Data Centers
    Water treatment
    Smart grid & LV Metering
    Photovoltaic & wind
  • Other Products In This Range


  • Product Specification

    Item Number

    83120138  

    Catalogue No.

    STPT12-12K275V-4PG  

    Item Description (ERP)

    STPT12-12K275V-4PG  

    Short Description

    SPD Type 1+2, 12.5kA, Uc275V, 3+1 TT, 4 Poles, 4 Modules, Pluggable  

    EAN/UPC Code

    8435297851523  

    ROHS Compliant

    Yes  

    IEC SPD Type

    Type 1+2 / Class I+II  

    Nominal Operating Volt Rating (Un)

    230 / 400   V

    AC or DC

    AC  

    Nominal Discharge Current (In) (8/20)

    20kA  

    Max Discharge Current : Imax (8/20)

    50kA  

    System Configuration

    TT. TNS  

    Lightning Impulse Current (10/350) (LIMP)

    12,5   kA

    Following Current (Ifi)

    0,1   kA

    Short Circuit Withstand (ISCCR)

    25   kA

    Indication System

    Yes  

    Indication System Type

    Visual Indicator  

    Number of Poles

    4-Pole  

    Torque Rating

    35.4   lb-in

    Max. Back-Up Fuse

    200 A gG  

    Housing Material

    PA66 CT1; V-0  

    Uc (L-N)

    275   V

    Uc (N-PE)

    255   V

    Up at In (N-PE)

    ≤1.5   kV

    Up at In (L-N)

    ≤1.3   kV

    Replacement Plug N-PE

    SP12-50K-N  

    Replacement Plug L-N

    SP12-12K275V  

    Product Weight

£460.18
  • Model: 83120138
***Please note. Our offices will be closed from 1pm 20th December - 08:15 2nd January for the holiday season. Last shipping date for pallets is 19 December, with smaller consignments 20 December. ***
We use cookies and other similar technologies to improve your browsing experience and the functionality of our site. Privacy Policy.